Shanghai Shenghua Cable (Group) Co., Ltd.

Manufacturer from China
Verified Supplier
9 Years
Home / Products / XLPE Insulated Power Cable /

3 Core Xlpe Insulated Pvc Sheathed Cable With Copper Tape Screen Medium Voltage Power Cable

Contact Now
Shanghai Shenghua Cable (Group) Co., Ltd.
Visit Website
City:shanghai
Province/State:hunan
Country/Region:china
Contact Person:MsMayling Zhao
Contact Now

3 Core Xlpe Insulated Pvc Sheathed Cable With Copper Tape Screen Medium Voltage Power Cable

Ask Latest Price
Video Channel
Brand Name :SHANCABLE
Model Number :YJV,YJLV
Certification :ISO,CE,IEC,TUV,KEMA
Place of Origin :Shanghai, China
MOQ :Negotiable
Price :Negotiable
Payment Terms :L/C, T/T
Supply Ability :100KM/Week
Delivery Time :10 Days
Packaging Details :Wooden Drum
Product Name :XLPE Insulation Electrical Power Cable
Nominal Area of Conductor :25mm2 to 1000 mm2
Test Voltage :21 kV/ 5min.
Standard :IEC 60502-2 ,IEC 60228
Application :For laying indoors and outdoors
Rated Voltage :6/10kV
Insulation :XLPE insulation
Drum Packing :Treaty steel wooden drum with good protection
Corporation :shenghua group
Brand :Sh Cable
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

XLPE Insulated Power Cable three core with copper tape screen medium voltage power cable

Description:

0.6/1kv XLPE Insulated Electric Power cable

CU/XLPE/PVC, IEC 60502

IEC 60502, IEC 60228, GB/T 12706.1-2008.

CE, CCC, KEMA. ISO

Constructions:

Conductor : Compact stranded copper conductor, Cl.2 as per IEC 60228
Insulation : XLPE(cross-linked polyethylene) rated at 90 ℃
Sheath : PVC type ST2 to IEC 60502, black

Note: Insulation color as per standards or customer requirement

Applications:

For laying indoors and outdoors. Able to bear certain traction during installation, but not external mechanical forces. Laying single core cable in magnetic ducts is not allowed.

Standards:

International: IEC 60502, IEC 60228

China: GB/T 12706.1-2008

Other standards such as BS,DIN and ICEA upon request

3 Core Xlpe Insulated Pvc Sheathed Cable With Copper Tape Screen Medium Voltage Power Cable

Technical data:

Rated voltage: 0.6/1kV

Max. Conductor Temp.: normal (90℃), short circuit no more than 5 s (160℃ when section-area

below 300mm2, 140℃ when section-area above 300mm2)

Min. Ambient Temp.:The cable shall be pre heated if the ambient temperature is below 0℃

Min. Bending Radius: single core cable 20(d+D)±5%

Multi-core cable 15(d+D)±5%

Certificates:

CE, RoHS, CCC, KEMA and more others at request

Technical Specifications:

Nom. Cross-section of conductor Insulation Thickness Sheath Thickness Approx. O.D. Approx.Weight Max. D.C Resistance of Conductor (20 ℃) Testing Voltage A.C Current Rating
mm2 mm mm (mm) kg/km Ω /km kV/5min In air (A) In soil(A)
1 × 25 3.4 2 20.0 598 0.727 21 140 150
1 × 35 3.4 2 22.0 719 0.524 21 175 180
1 × 50 3.4 2 23.0 884 0.387 21 205 215
1 × 70 3.4 2 24.0 1097 0.268 21 260 265
1 × 95 3.4 2 26.0 1378 0.193 21 315 315
1 × 120 3.4 2 28.0 1658 0.153 21 365 360
1 × 150 3.4 2 30.0 1967 0.124 21 415 405
1 × 185 3.4 2 31.0 2335 0.0991 21 475 455
1 × 240 3.4 2 34.0 2908 0.0754 21 565 530
1 × 300 3.4 2 36.0 3507 0.0601 21 645 595
1 × 400 3.4 2.5 39.0 4503 0.0470 21 750 680
1 × 500 3.4 2.5 42.0 5479 0.0366 21 865 765
1 × 630 3.4 2.5 48.0 6952 0.0283 21 990 860
1 × 800 3.4 2.6 52.0 7120 0.0221 21 1140 950
1 × 1000 3.4 2.8 57.0 10500 0.0176 21 1250 1040
3 × 25 3.4 2.3 41.0 895 0.727 21 120 125
3 × 35 3.4 2.4 44.0 2293 0.524 21 145 155
3 × 50 3.4 2.5 46.0 2812 0.387 21 175 180
3 × 70 3.4 2.6 50.0 3508 0.268 21 220 220
3 × 95 3.4 2.7 53.0 4402 0.193 21 265 265
3 × 120 3.4 2.8 56.0 5319 0.153 21 305 300
3 × 150 3.4 2.9 59.0 6309 0.124 21 350 340
3 × 185 3.4 3.0 62.0 7319 0.0991 21 395 380
3 × 240 3.4 3.2 68.0 9218 0.0754 21 470 435
3 × 300 3.4 3.4 72.0 11159 0.0601 21 535 485
3 × 400 3.4 3.6 81.0 15107 0.0470 21 610 520