Shanghai Shenghua Cable (Group) Co., Ltd.

Manufacturer from China
Verified Supplier
10 Years
Home / Products / Low Smoke Zero Halogen Cable /

0.6 / 1 KV XLPE / LSHF Low Smoke Halogen Free Cable Underground PO Jacket

Contact Now
Shanghai Shenghua Cable (Group) Co., Ltd.
Visit Website
City:shanghai
Province/State:hunan
Country/Region:china
Contact Person:MsMayling Zhao
Contact Now

0.6 / 1 KV XLPE / LSHF Low Smoke Halogen Free Cable Underground PO Jacket

Ask Latest Price
Brand Name :SHANCABLE
Model Number :WDZA-YJY
Certification :KEMA,ISO,CE,IEC,PICC
Place of Origin :SHANGHAI, CHINA
MOQ :1000meters
Price :US$1.0~120per meter
Payment Terms :L/C, T/T
Supply Ability :30Kilometer/Month
Delivery Time :Depending on order quantity
Packaging Details :Iron-wooden drum
Conductor Type :Stranded Class2
Cores :Muti-cores
Insulation Material :XLPE
Jacket :PO
Function :LSHF
Standard :IEC
Working temperature :90℃
Corporation :shenghua group
Brand :Sh Cable
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

0.6/1 KV XLPE / LSHF Low Smoke Halogen Free Power Cable Underground

Main features
1. Ordinary flame retardant cable
For Class A and Class B fire tests, the fire time is 40 minutes, and for Class C and Class D fire tests, the fire time is 20 minutes, and the charring height does not exceed 2.5 m.
2. Low-halogen low-smoke flame retardant cable
Halogen acid gas emission <100 mg/g, smoke density (transmittance) > 30%, from the group burning test, it meets the requirements of Class C flame retardancy.
3. Low smoke zerohalogen (LSZH) flame retardant cable:
Halogen acid gas all-emission 0 mg/g, pH value ≥ 4.3, conductivity ≤ 10 us/mm, toxicity index ≤ 5. From the group burning test, it at least meets the requirements of Class C flame retardancy, smoke density (transmittance) ≥
60%.
4. Oxygen barrier cable (highly-flame retardant cable)
From the group burning test, it meets and exceeds the requirements of Class A flame retardancy, and the smoke density (transmittance) is equal to or close to national standard GB/T17651-2008 and international standard IEC61034 low smoke standard.
It is especially suitable for 6 KV-35 KV medium-voltage cable frame retardancy, has not only flame retardancy up to Class A, but also has certain refractory characteristics (i.e. can still keep 2.4 Uo insulation standard after burning for 20 min).
Notes: Users can select category and class of flame retardant cable according to laying places.

-> Using condition:
1. AC rated voltage: U0 /U (V series: 600/1000V, K series: 450/750V, B series: 450/750V).
2. long working temperature of cable:
(1) the insulation and sheath of vinyl fluoride: 70℃ and 105℃;
cross linked polyethylene(XLPE) insulation: 90℃;
(2) fluoroplastic insulated and sheathed: 220℃ and 260℃;
fluorine plastic insulation and 105℃ flame retardant poly vinyl fluoride sheath: 90℃ and 125℃.
(3) low halogen low smoke flame retardant PVC insulated and sheathed: 70 ℃;
non halogen low smoke flame retardant polyolefin insulation and sheath: 90℃ and 125℃.
3. minimum ambient temperature:
(1) flame retardant PVC insulation and sheath: fixed laying: -40℃; non-fixed laying: -15℃;
(2) fluorine plastic insulation and sheath: fixed laying: -60℃;
non-fixed laying: -20℃;
4. the temperature of cable laying should not be less than 0℃.

0.6 / 1 KV XLPE / LSHF Low Smoke Halogen Free Cable Underground PO Jacket

Inquiry Cart 0